Spoolset › Charts › Schedule 40 pipe dimensions
Schedule 40 pipe dimensions
Twelve nominal sizes, with the bore and the volume derived from the two published figures rather than looked up separately.
Every figure on this page is produced by the same code as the Spoolset app — not re-typed from it.
Schedule 40, ASME B36.10M
| Size | Outside dia. | Wall | Bore |
|---|---|---|---|
| 1/2" | 0.840″ | 0.109″ | 0.622″ |
| 3/4" | 1.050″ | 0.113″ | 0.824″ |
| 1" | 1.315″ | 0.133″ | 1.049″ |
| 1-1/4" | 1.660″ | 0.140″ | 1.380″ |
| 1-1/2" | 1.900″ | 0.145″ | 1.610″ |
| 2" | 2.375″ | 0.154″ | 2.067″ |
| 2-1/2" | 2.875″ | 0.203″ | 2.469″ |
| 3" | 3.500″ | 0.216″ | 3.068″ |
| 4" | 4.500″ | 0.237″ | 4.026″ |
| 5" | 5.563″ | 0.258″ | 5.047″ |
| 6" | 6.625″ | 0.280″ | 6.065″ |
| 8" | 8.625″ | 0.322″ | 7.981″ |
Schedule 40 is the default weight for most plumbing and low-pressure process work, and it is what the take-out tables assume as the mating pipe.
Bore area and volume
| Size | Bore area | US gal/ft | Litres/ft |
|---|---|---|---|
| 1/2" | 0.304 in² | 0.0158 | 0.0598 |
| 3/4" | 0.533 in² | 0.0277 | 0.1049 |
| 1" | 0.864 in² | 0.0449 | 0.1700 |
| 1-1/4" | 1.496 in² | 0.0777 | 0.2941 |
| 1-1/2" | 2.036 in² | 0.1058 | 0.4003 |
| 2" | 3.356 in² | 0.1743 | 0.6599 |
| 2-1/2" | 4.788 in² | 0.2487 | 0.9415 |
| 3" | 7.393 in² | 0.3840 | 1.4537 |
| 4" | 12.730 in² | 0.6613 | 2.5033 |
| 5" | 20.006 in² | 1.0393 | 3.9340 |
| 6" | 28.890 in² | 1.5008 | 5.6811 |
| 8" | 50.027 in² | 2.5988 | 9.8375 |
These three columns are arithmetic, not lookups: bore is
OD − 2 × wall, area is π × (bore/2)², and a US gallon is 231 in³, so
gallons per foot is area × 12 / 231. Nothing here can disagree with the table
above it.
Why the outside diameter does not change with schedule
Nominal Pipe Size is a name, not a measurement — 2″ pipe has an outside diameter of 2.375″ in every schedule. Only the wall thickness changes, inward, so the bore shrinks while the fitting that goes over it stays the same. That is what makes schedules interchangeable at a joint and why a take-out is a function of NPS alone.
Below about 12″ the nominal size bears no useful relation to any dimension of the pipe. At and above 14″ it becomes the outside diameter exactly — which is outside the range of this table.
Related charts
Schedule 80 dimensions
The same twelve sizes with the heavier wall, and what it costs you in bore.
Pipe volume per foot
Gallons and litres per foot, derived from the bore.
Elbow take-out chart
ASME B16.9 long-radius centre-to-face, ½″ through 8″.
2" pipe data
Outside diameter, wall, bore, volume and the B16.9 elbow take-outs.
Do this on the job, not at a desk
Spoolset runs these calculations on an iPhone and draws the shape to scale as you type, so a mistyped number shows up as a wrong picture. It cites the source of every table it uses. Simple offsets and grade are free; rolling offsets and the take-out tables are a one-time purchase.